IKO enertherm KR ALU beneath underfloor heating: checks before screeding
PIR insulation
IKO enertherm KR ALU forms an insulating layer below the heated screed. The printed grid helps the installer follow the pipe layout on the heating drawings. Before ordering, check the depth available at the door for insulation, pipes, screed and floor finish. Compare both sides of the threshold, particularly where tile meets timber. Before screeding, the board support, movement joints and actual pipe routes are still visible. Once the screed has set, reaching these details means opening the floor.

What to settle before delivery
Measure from the highest point of the prepared base. Agree the position of the pipes within the screed with the heating contractor so their depth is counted only once.
Identifying the board and its declared properties
KR ALU has a gridded aluminium facing, λD of 0.022 W/(m·K), a compressive stress of at least 150 kPa at 10% deformation and reaction to fire class F.
Using a worked example
The KR ALU table gives declared RD values of 3.60 and 4.50 m²K/W for 80 and 100 mm respectively. The extra 20 mm therefore adds 0.90 m²K/W of resistance in the insulation layer.
Using nominal conductivity for 100 mm gives about 4.55 m²K/W. Compare quotations using the declared 4.50 and mark the finished floor level for each option.
Comparing the available options
If depth at the doorway is limited, work through alternatives with the floor designer. Show insulation thickness, specified pipe cover and the transition between finishes for each option.
Inspection before covering
Before pouring, inspect the manifold area and doorways. Compare pipe spacing with the drawings, check board support between service runs and record the circuit leak test result.
What the quote should cover
Price the KR ALU layer separately from the heating installation and screed. Define the base preparation and who forms the movement joint at the threshold.
Records to keep after completion
Attach photographs of the loops with dimensions from a permanent wall. Together with the manifold circuit labels, they help locate pipes during later work.
Free quote
What to include in your enquiry
Tell us how you plan to use the material, the dimensions and the quantity you need. Include the thickness, grade or variant name, along with the delivery town or your preferred collection branch. For a specific product, add its name or a link to the product page. We will reply to the email address you provide to discuss availability and the terms of your order.
More from the building guide
To decide whether an existing sill will work with SOPREMA EFIGREEN ITE, measure its projection from the future façade face. On a…
PIR can save headroom in a loft, but a thickness comparison only answers the thermal question. For example, at conductivities of 0.022…
PIR sandwich panels form a building envelope from metal facings and an insulating core. Wall and roof panels differ in profile, joints…
Effective roof insulation forms a continuous boundary around heated rooms, rather than merely a thick layer across the middle of a slope.…
Schedule IKO enertherm ALU TAP from the outlet towards the high edge of each drainage area. Two tapers can have the same…
Replacing hall walls or roofing with PIR-core panels requires both an envelope design and a plan for keeping the building protected during…
After insulating a home, check both energy consumption and the cost of purchasing it. A lower bill alone does not prove that…
Attic insulation works when it forms a continuous layer and the entire roof manages moisture and air leakage. A thicker board cannot…