IDELCO α-therm WALL in a cavity wall: detailing the window sill

PIR insulation

At a glance

A single window reveals much about how IDELCO α-therm WALL fits into a cavity wall. A section below the sill shows where the insulation ends, how much space remains behind the outer leaf and where rain entering through façade joints will drain. The reveal also needs cuts and allowances for wall ties. Ask the crew to show you this junction before building further courses of facing masonry. At that stage you can still see board contact, tongue-and-groove joints and whether the designed cavity is clear.

IDELCO α-therm WALL insulation board with its facing

Position of α-therm WALL in masonry

Label the structural leaf, insulation and outer masonry leaf. Show where wall ties are anchored and how they pass through the insulation.

Conductivity and junction geometry

For 100 mm α-therm WALL the sheet gives RD 4.50 m²K/W and λD 0.022 W/(m·K). Record both beside the thickness on the schedule.

A separate sill detail is needed because heat also passes through the frame and masonry there. Board resistance alone cannot give the internal corner temperature.

Tongue-and-groove joints

Lay out the 1200 × 600 mm boards from the reveal into the wall field. Mark which edge of the first cut piece retains its factory profile.

Trial-fitting two boards exposes a damaged tongue before concealment. Finish the cut edge at the frame to the specified reveal detail.

Drainage below the sill

Check where the sill flashing ends and discharges. Water behind the outer leaf needs an outward drainage path at the lower window corners as well.

Clear mortar droppings and insulation scraps from the drainage path. Inspect the cavity base while it is still accessible from above.

Properties of the wall board

WALL is declared at least 120 kPa at 10% deformation and reaction to fire class F. Use the sheet naming this wall variant for handover.

Wall tie capacity and wall fire resistance each need evidence for the relevant system. Neither follows from a board compression test.

Quantities and inspection before concealment

Subtract openings from wall area and measure insulated reveals separately. For repeated windows, plan cuts around one opening before multiplying quantities.

Agree an inspection stage, such as completion of the course below the windows. A photograph with a scale records cavity width and the edge board position.

Checking the sill projection

If a window change leaves the sill shorter, revisit the section. Check projection beyond the finished façade and drip position before ordering all the flashings.

7 branches. Materials closer to your project.

  • SEROCK — Dzierżenin 34 E [mapa]
  • BŁONIE — ul. Sochaczewska 138A [mapa]
  • RADOM — ul. Grobickiego 8 [mapa]
  • ŁÓDŹ — Natolin 8 [mapa]
  • OLSZTYN — Barczewo, ul. Prosta 9 [mapa]
  • WROCŁAW — ul. Jerzmanowska 10C [mapa]
  • GORZÓW WLKP. — ul. Zielona 33/34 [mapa]
Budowlanka.org — map

Free quote

What to include in your enquiry

Tell us how you plan to use the material, the dimensions and the quantity you need. Include the thickness, grade or variant name, along with the delivery town or your preferred collection branch. For a specific product, add its name or a link to the product page. We will reply to the email address you provide to discuss availability and the terms of your order.

More from the building guide